Fluke 1625-2 GEO Earth Ground Tester
Key features
Key features
- A unique earth ground tester that performs testing with and without stakes
- Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
- Performs selective earth ground rod testing (one clamp + stakes)
- Performs stakeless earth ground rod testing (two clamps)
- Features Automatic Frequency Control (AFC) to minimize the effect of interference
Product overview: Fluke 1625-2 GEO Earth Ground Tester
Get fast, accurate earth ground testing using all four test methods
The Fluke 1625-2 earth ground tester measures earth ground loop resistances using only clamps, only stakes, or one clamp and stakes. With the stakeless test method, the Fluke 1625-2 is able to measure earth ground loop resistances for multi-grounded systems using only current clamps. This technique eliminates the dangerous, and time consuming job of disconnecting parallel grounds, and finding suitable locations for auxiliary ground stakes. This allows you to perform earth ground tests in places you’ve not considered before, such as inside buildings, on power pylons, or anywhere you don’t have access to soil.
Keep your options open
If a bonded earth ground system does not exist for the building or structure under test, and there is only one path to ground, you can use the 1625-2 to perform the fall-of-potential test method with stakes.
The 1625-2 Earth Ground Tester offers other advanced features including:
- Automatic Frequency Control to identify existing interference and choose a measurement frequency to minimize its effect, thus providing a more accurate earth ground value.
- R* measurement that calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see.
Other useful capabilities:
- Provides R* measurement that calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see
- Includes USB port for data storage and transfer
- Features IP56 rating for outdoor use
- Offers adjustable limits for quicker testing
- Comes with a rugged carrying case
Specifications: Fluke 1625-2 GEO Earth Ground Tester
General Specifications | ||||
Memory | Internal memory storage up to 1500 records accessible via USB port | |||
Measuring function | Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with AC, 2- and 4-pole with DC | |||
Display | 4 digit (2999 Digit) - 7 segment liquid crystal display, with improved visibility | |||
Operation | Central rotary switch and function keys | |||
Temperature Range | ||||
Operating temperature | -10°C to 50°C (14°F to 122°F) | |||
Storage temperature | -30°C to 60°C (-22°F to 140°F) | |||
Temperature coefficient | ±0.1% of reading/°C < 18°C > 28°C | |||
Type of protection | IP56 for case, IP40 for battery door according to EN60529 | |||
Max voltage | Warning – socket "clamp" to socket E, ES, S or H | |||
Urms = 0 V | ||||
Sockets E, ES, S or H to each other in any combination, max. Urms = 250 V (pertains to misuse) | ||||
Safety | Protection by double and/or reinforced insulation. Max. 50 V to earth per IEC61010-1. Pollution degree 2 | |||
Quality standard | Developed, designed and manufactured to comply with DIN ISO 9001 | |||
External field influence | Complies with DIN 43780 (8/76) | |||
Auxiliary power | 6 x 1.5 V alkaline (IEC LR6 or type AA) | |||
Battery life span | With IEC LR6/type AA: typ. 3,000 measurements (RE+RH ≤ 1 kΩ) | |||
With IEC LR6/type AA: typ. 6,000 measurements (RE + RH > 10 kΩ) | ||||
Dimensions (W x H x D) | 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in) | |||
Weight | ≤ 1.1 kg (2.43 lb) without accessories 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case | |||
Case material | Polyester | |||
Measurement of Interference Voltage DC + AC (UST) | ||||
Measuring limits of error: method | Full wave rectification | |||
Measuring range | 1 V to 50 V | |||
Display range | 0.0 V to 50 V | |||
Resolution | 0.1 V | |||
Frequency range | DC/AC 45 Hz to 400 Hz sine | |||
Accuracy | ±(5% of rdg + 5 digit) | |||
Measuring sequence | Approx. 4 measurements/s | |||
Internal resistance | Approx. 1.5 MΩ | |||
Max. overload | Urms = 250 V | |||
Measurement of Interference Frequency (F) | ||||
Measuring limits of error: method | Measurement of oscillation period of the interference voltage | |||
Measuring range | 6.0 Hz to 400 Hz | |||
Display range | 16.0 Hz to 299.9 Hz to 999 Hz | |||
Resolution | 0.1 Hz to 1 Hz | |||
Range | 1 V to 50 V | |||
Accuracy | ±(1% of rdg + 2 digit) | |||
Earthing Resistance (RE) | ||||
Measuring method | Current and voltage measurement with probe as IEC61557-5 | |||
Open circuit voltage | 20/48 V, AC | |||
Short circuit current | 250 mA AC | |||
Measuring frequency | 94, 105, 111, 128 Hz selected manually or automatic. (AFC) 55 Hz in function R1 | |||
Noise rejection | 120 dB (16 2/3 , 50 , 60, 400 Hz) | |||
Max. overload | Urms = 250 V |
Models: Fluke 1625-2 GEO Earth Ground Tester
Fluke 1625-2
Fluke 1625-2 GEO Earth Ground Tester
Includes:
- GEO Earth Ground Tester
- User's Manual
- Batteries
- Quick Reference Guide
- USB Cable
View more about Fluke 1625-2 GEO Earth Ground Tester on main site